Model Number :CKVB-24/GB
Certification :Type Test Report
Place of Origin :China
Payment Terms :L/C, T/T, Western Union
Packaging Details :Wooden Packing
MOQ :1set
Price :To be discussed later
Delivery Time :10-15 work days
Rated voltage :24kV
Rated current :630A,1250A
Rated frequency :50Hz
Type :Indoor
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

1. CKVB-24/GB is the withdrawable circuit breaker.

2. Technical Data

Description Unit Parameter
Rated voltage kA 24
Rated short-time withstand voltage phase-to-phase phase-to-earth kA 65
open contact kA 79
Rated lighting impulse withstand voltage phase-to-phase phase-to-earth kA 125
open contact kA 145
Rated frequency Hz 50
Pole centre distance mm 210, 230
Rated current A 630 1250
Rated short-time withstand current(4s) kA 25 31.5 25 31.5
Rated peak withstand current kA 63 80 63 80
Rated short-circuit breaking current kA 25 31.5 25 31.5
Rated short-circuit making current kA 63 80 63 80
Rated breaking cable charging current A 25
Rated capacitor bank inrush making current kA 12.5
Rated single capacitor bank breaking current A 630
Rated back to back capacitor bank breaking current A 400
Operating sequence / Opening-0.3s-Closing/Opening-180s-Closing/Opening
Mechanism life times 20000
Opening times for rated current times 20000
Opening times for rated short-circuit current times 50
Clearance between open contacts mm 13±1
Overtravel mm 4±1
Average closing speed m/s 0.8~1.2
Average opening speed m/s 1.1~1.7
Closing time ms 35~70
Opening time ms 20~50
Bounce time for contact’s closing ms ≤2
Asynchronous time for three-phase contacts closing / opening ms ≤1
Allowable accumulated wearing thickness of moving/fixing contact mm 3


3. Standard

---- GB1984-2003

---- IEC60056-2001

---- GB/T16927-1997

----GB/T 4473-2008

---- DL/T403-2000

---- JB/T3855-2008

4. Working Condition

4.1 Ambient air temperature: -25℃~+40℃

4.2 Ambient humidity:

---- relative average daily humidity: ≤95%

---- relative average daily water vapor pressure: ≤2.2kPa

---- relative average monthly humidity: ≤90%

---- relative average monthly water vapor pressure: ≤1.8kPa

4.3 Altitude: ≤1000m

4.4 Earthquake intensity: ≤magnitude 8

4.5 Ambient air doesn’t obviously pollute by dust, smoke, corrosive or combustible gas, vapors or salt spray.

(Exceeding above working condition is available as customized product)